Treffer: Automation of cycles of protections' non-traditional tests using traditional injectors and electromagnetic transient programs via Python.

Title:
Automation of cycles of protections' non-traditional tests using traditional injectors and electromagnetic transient programs via Python.
Source:
Journal of Electrical Engineering; Oct2025, Vol. 76 Issue 5, p409-419, 11p
Database:
Complementary Index

Weitere Informationen

This article shows a method to perform cycles of non-traditional tests to electric power system protections, in an automated way, using traditional injectors and Electro-Magnetic Transient Software (EMTS) via Python. Non-traditional tests of protective relays, using non-sinusoidal current and voltage waveforms computed from an EMTS, have been performed since the invention of programmable injectors but different non-obvious steps are necessary for this purpose (the obtained files from the EMTS must be converted to a standardized format to be transferred to the injector, injected to the relay under test, and the relay contacts have to be monitored in order to record their operation or non-operation, and/or to record their operation time). In order to easily perform repetitive cycles of these non-traditional tests, with different conditions of simulation in the EMTS, these steps were automated using Python, which is simply applied to control the injector and the EMTS in a loop. This method is suitable for different practical cases, and it is useful to avoid some costs and disadvantages related to the use of real-time simulation (which probably is the most known alternative to perform these cycles of tests). Herein, the obtainment of tripping times of distance protections as a function of fault location and source impedance in case of a series-compensated line is shown as an example. The results were obtained for mho and quadrilateral characteristics of three commercial relays, using a very basic injector and a royalty-free EMTS in order to illustrate that the tests can be performed with very low resources. The proposed method is considerably less expensive than the use of real-time digital simulators, and considerably faster than the use of the same resources without the proposed automation, which currently are the main available methods for these tests. [ABSTRACT FROM AUTHOR]

Copyright of Journal of Electrical Engineering is the property of Sciendo and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)